The Hioki PQ3198 is a professional-grade, high-performance power quality analyzer designed for monitoring and recording power supply anomalies, enabling rapid investigation of issues such as voltage drops, flickers, harmonics, and transient overvoltages. Operating in full compliance with the strict IEC61000-4-30 Class A standard, it offers unparalleled precision, standard-compliant recording, and synchronous 4-channel voltage/current inputs.

Specifications

General

ParameterValue
InterfacesLAN (100Base-TX), USB 2.0 (Device), SD/SDHC Card Slot, RS-232C (for GPS synchronization)
Display6.5-inch color TFT LCD (640 × 480 dots)

Physical

ParameterValue
Power SupplyAC Adapter Z1002 (100 V to 240 V AC, 50/60 Hz, max 40 VA), Battery Pack 9780 (7.2 V DC)
Operating Temperature-20 °C to 50 °C
Dimensions (W×H×D)300 mm × 211 mm × 68 mm
Weight2.2 kg (including Battery Pack 9780)

Input Channels & Configuration

ParameterValue
Number of Voltage Inputs4 channels (Ch 1, Ch 2, Ch 3: common ground; Ch 4: isolated)
Number of Current Inputs4 channels
Phase Configurations SupportedSingle-phase 2-wire, Single-phase 3-wire, Three-phase 3-wire, Three-phase 4-wire

Measurement Ranges & Input Characteristics

ParameterValue
Direct Voltage Range1000.0 V rms
Direct Current Range500.00 mA to 5.0000 kA AC (clamp sensor dependent)
Transient Voltage Range6.0000 kV peak
Voltage Input Impedance2.0 MΩ ±10% (for all voltage input channels)
Voltage Crest Factor3 or less
Maximum Input Voltage1000 V AC / DC

Measurement Performance & Accuracy

ParameterValue
Transient Sampling Rate2 MHz (0.5 μs cycle)
Power Sampling Rate200 kHz (5 μs cycle)
A/D Converter Resolution16-bit
Basic Frequency Range45 Hz to 66 Hz
Voltage Measurement Accuracy±0.1% of nominal voltage
Current Measurement Accuracy±0.1% rdg. ±0.1% f.s. + clamp sensor accuracy
Active Power Accuracy±0.2% rdg. ±0.1% f.s. + clamp sensor accuracy

Power & Harmonic Analysis Functions

ParameterValue
Harmonic Measurement Bandwidth1st to 50th order
High-order Harmonic Range2 kHz to 80 kHz (voltage and current)
Flicker Measurement ComplianceIEC 61000-4-15 (Pst, Plt)
Unbalance MeasurementVoltage and current unbalance (zero-phase and negative-phase components)
Swell/Dip/Interruption Resolution0.5-cycle interval recording

Data Logging, Memory & Visualization

ParameterValue
Internal Storage Capacity60 MB
External Storage CompatibilitySD/SDHC card (up to 32 GB)
Maximum Logging DurationUp to 1 year (dependent on SD card capacity and parameter settings)

Power Supply & Safety Compliance

ParameterValue
Safety Category RatingCAT IV 600 V, CAT III 1000 V
Safety Standards ComplianceEN 61010-1
EMC Standards ComplianceEN 61326-1 Class A
Battery Continuous Operation TimeApprox. 180 min (using Battery Pack 9780)

Physical & Environmental Specifications

ParameterValue
Storage Temperature Range-30 °C to 60 °C
Operating Humidity Range80% rh or less (non-condensing)
IP RatingIP30 (EN 60529)

Performance

ParameterValue
Maximum Recordable Events9999
Clock Accuracy±0.3 s/day (power ON), ±1.0 s/day (power OFF, 23 °C)
GPS Synchronization AccuracyWithin ±13 μs (with optional GPS Box PW9005)
Transient Overvoltage Peak Measurement RangeUp to 6.000 kV peak
Transient Overvoltage Minimum Detection Width0.5 μs

Inputs & Outputs

ParameterValue
External Control TerminalsEvent input ×1, Event output ×1
USB Interface TypeUSB 2.0 (High Speed, mini-B connector)
LAN Interface Type100Base-TX

Safety

ParameterValue
Maximum Rated Voltage to Earth1000 V AC / DC (CAT III), 600 V AC / DC (CAT IV)

Power

ParameterValue
Maximum Power Consumption80 VA max.
Battery Charging TimeApprox. 5.5 hours (at 23 °C with power OFF)

Display

ParameterValue
Display Resolution640 × 480 dots (VGA)
Display LanguagesEnglish, Japanese, Chinese (Simplified/Traditional), Korean, German, French, Italian, Spanish, Turkish

Logging & Memory

ParameterValue
Recording Interval Settings1 s, 3 s, 15 s, 30 s, 1 min, 5 min, 10 min, 15 min, 30 min, 1 h, 2 h, 150/180 cycles

Connectivity & Control

ParameterValue
Web Server FunctionYes (allows remote configuration and monitoring via web browser)
FTP FunctionalityFTP Server and FTP Client
Modbus/TCP SupportYes
E-mail NotificationYes (sends emails on event occurrences)

Power & Battery

ParameterValue
Battery Pack ModelZ1003 Battery Pack (Lithium-ion)

Measurement Performance

ParameterValue
Harmonic Analysis Orders1st to 50th order
Inter-harmonic Analysis Orders0.5th to 49.5th order

General Specifications

ParameterValue
Real-Time Clock Backup Battery LifeApprox. 10 years (referenced to 23 °C)

Technology

Power Quality Analyzer

Applications

Electrical grid monitoring, power quality troubleshooting, energy audits, and testing of power distribution systems.