The Sorensen DCR60 series (comprising phase-controlled SCR models such as the DCR 60-1.5B, DCR 60-3B, DCR 60-7B, DCR 60-14B, DCR 60-45B, and DCR 60-115B) provides highly regulated, precise, and adjustable DC output up to 60V. Utilizing Silicon Controlled Rectifier (SCR) or Triac technology at the transformer input followed by a passive LC filter, the DCR60 series delivers highly efficient regulated power with excellent transient recovery times and automatic crossover between voltage and current modes.

Specifications

General

ParameterValue
InterfacesAnalog remote programming (voltage, resistance), remote sensing
DisplayDual front-panel analog meters (voltage and current); optional digital meters

Physical

ParameterValue
Power Supply115 VAC ±10% single-phase standard, 50/60 Hz; optional 208/220/230 VAC inputs
Operating Temperature0 to 70 °C
Dimensions (W×H×D)Benchtop or 19-inch rackmount (height and depth vary by current rating option)

Output Specifications

ParameterValue
Rated Output Voltage Range0 to 60 VDC
Line Regulation (Voltage)0.05% of maximum output voltage (30 mV) for a ±10% line change
Load Regulation (Voltage)0.05% of maximum output voltage (30 mV) for a 0 to 100% load change
Line Regulation (Current)0.15% of maximum output current for a ±10% line change
Load Regulation (Current)0.15% of maximum output current for a 100% compliance voltage change
Temperature Coefficient (Voltage)0.015% of maximum output voltage per °C
Temperature Coefficient (Current)0.05% of maximum output current per °C
Transient Recovery Time50 ms (typical, for a 50% step load change to return to within 1% of rated voltage)
Remote Sense CompensationUp to 1 V drop per output lead
Operating ModesConstant Voltage (CV) and Constant Current (CC) with automatic crossover

AC Input Specifications

ParameterValue
Input Voltage Range115 VAC ±10% standard (208 / 220 / 230 VAC optional)
Input Frequency Range47 to 63 Hz

Protection and Diagnostics

ParameterValue
Over Voltage Protection (OVP) Range6V to 80V (approximate, adjustable crowbar)
Output Isolation Voltage700 VDC maximum from output to chassis ground

Control and Interface

ParameterValue
Remote ShutdownSupported via rear-terminal contact closure or TTL signal
Series/Parallel OperationCapable of series or parallel configuration for increased voltage or current

Environmental and Safety

ParameterValue
Operating Temperature Range0 °C to +70 °C (full performance to 50 °C; derate linearly from 50 °C to 40% load at 70 °C)
Storage Temperature Range-40 °C to +85 °C
Cooling SystemConvection or internal fan (model and current rating dependent)

Physical Characteristics

ParameterValue
Front Panel ControlsPower circuit breaker, Coarse and Fine Voltage potentiometers, Coarse and Fine Current potentiometers, OVP adjust (screwdriver slot)

Technology

Phase-Controlled SCR

Applications

Industrial burn-in, battery charging, electroplating, magnet supplies, and general-purpose laboratory R&D