The Tektronix TCP0150 is a high-performance 150 A AC/DC current probe designed specifically for use with the TekVPI™ oscilloscope interface. With a bandwidth of DC to 20 MHz, it provides excellent accuracy and high sensitivity for measuring both low-level currents down to 5 mA and high-power currents up to 300 A peak. The probe is powered directly by the oscilloscope and features automatic scaling, on-screen readout, and integrated degaussing/auto-zero controls.

Specifications

General

ParameterValue
InterfacesTekVPI interface

Physical

ParameterValue
Power SupplyPowered directly via TekVPI probe interface
Operating Temperature0 °C to 50 °C
Weight0.66 kg
Jaw Opening21 mm

Electrical & Measurement Performance

ParameterValue
BandwidthDC to >=20 MHz
Rise Time<=17.5 ns
Maximum Continuous Current (RMS)150 A
Maximum Peak Pulse Current300 A
Minimum Measurable Current5 mA
Measurement Ranges25 A / 150 A
DC Accuracy±3% (typical ±1%)
Amp-Second Product3000 A·µs (150 A range), 500 A·µs (25 A range)
Propagation Delay17 ns (typical)
Insertion Impedance (1 MHz)0.03 Ω
Insertion Impedance (10 MHz)0.12 Ω
Insertion Impedance (20 MHz)0.3 Ω
Maximum Bare Wire Voltage300 V RMS CAT II
Signal CouplingAC, DC
Output Impedance50 Ω
Random Noise (25 A Range)≤2.5 mA RMS
Random Noise (150 A Range)≤12.5 mA RMS

Interface & Compatibility

ParameterValue
Interface TypeTekVPI
Power RequirementsPowered directly by TekVPI host oscilloscope
Host Oscilloscope CompatibilityTektronix oscilloscopes with TekVPI probe interface
Automatic Scaling SupportYes (automatic units and scaling on oscilloscope screen)

Control & Operation

ParameterValue
Degauss and Auto-Zero ControlsButton on probe compensation box
Range Selection ControlsButton on probe compensation box or via oscilloscope menu
Status Indicator LEDsYes (Degauss/AutoZero status, 25 A range, 150 A range)
Jaw Open/Closed DetectionYes

Physical & Mechanical

ParameterValue
Maximum Conductor Diameter21 mm (0.83 in)
Probe Head Length26.8 cm (10.55 in)
Probe Head Width4.1 cm (1.6 in)
Probe Head Height6.8 cm (2.7 in)
Probe Cable Length2 m (6.6 ft)
Probe Head Weight0.66 kg (1.45 lb)

Environmental Specifications

ParameterValue
Storage Temperature-40 °C to 75 °C (-40 °F to 167 °F)
Operating Humidity5% to 95% RH (non-condensing) up to +30 °C; 5% to 85% RH from +30 °C to +50 °C
Storage Humidity5% to 95% RH (non-condensing) up to +30 °C; 5% to 85% RH from +30 °C to +75 °C
Operating AltitudeUp to 2,000 m (6,560 ft)
Storage AltitudeUp to 12,192 m (40,000 ft)

Regulatory & Safety Compliance

ParameterValue
Safety CertificationsUL61010-2-032, CSA61010-2-032, EN61010-2-032, IEC61010-2-032
Pollution Degree2
RoHS CompliantYes

Ordering & Maintenance

ParameterValue
Standard AccessoriesProbe cover, instruction manual, certificate of calibration
Warranty Period1 year

Electrical Characteristics

ParameterValue
Maximum Insulated Wire Voltage600 V RMS CAT II

Performance

ParameterValue
Typical DC Accuracy±1.5% of reading ±50 mA
DC Accuracy Temperature Range23 °C ±5 °C
Minimum Sensitivity5 mA (on oscilloscopes supporting 1 mV/div)
Typical Gain Drift<2.5% (over 0 °C to 50 °C operating range, after 20-minute warm-up)

Physical Characteristics

ParameterValue
Compensation Box Length107 mm
Compensation Box Width41 mm
Compensation Box Height26 mm

Safety & Compliance

ParameterValue
EMC ComplianceEC Council Directive 2004/108/EC, FCC Part 15 Class A, EN61326-1, EN61326-2-1, AS/NZS CISPR 11

Technology

Split-core Hall-effect and transformer AC/DC current sensing

Applications

Power supply design, motor drive analysis, power electronics, and industrial maintenance